Ruixue developed 3 series New Air coolers to satisfy all refrigeration requirements in highmedium and low temperature application and in different humidity conditions.

4.5mm/YED-A Series=Fin spacing=4.5mm
7mm/YED-C Series=Fin spacing=7mm
10mm/YED-D Series=Fin spacing=10mm

High-efficiency inner grooved copper tube and wave aluminium fins had been used for designing evaporators the higher heat transfer efficiency can be achieved.

High quality distributor selecting and refrigeration system optimizing ensure maximum efficiency of evaporator in various applications of Air coolers.

Hidria axial fans were matched to new Air coolers this will lead to new features for air coolers-high efficiency and saving energy. In addition we can customize product using other brand fan in line with requirement of customer.

Defrost stainless electrical heaters were put into aluminum tubes ensure defrost heat to utilizing fully and sgnificantly reducing loss.

Strength Design could reduce vibration and noise level effectively. Hinge parts make check maintenance and cleaning more easily.

YED-A Series(fin spacing=4.5mmR404A)

TypeSC1SC2SurfaceTube volumeFan
Fan Qty.

Air
flow

Air
throw

Noise
Fan InputFan Current
Fan Supply Power
(kW)(kW)(m2)(l)φ(mm)(m3/h)(m)(dB(A))(W/pcs)(A/pcs)
YED-M142AE-2524.53.117.94.425021495652550.31P-220/230V 50Hz
YED-M143AE-3028.05.426.96.430022748857850.31P-220/230V 50Hz
YED-M143AE-30310.38.140.39.2300341501059850.31P-220/230V 50Hz
YED-M164AE-40218.313.959.913.84002567010692050.71P-220/230V 50Hz
YED-M144AE-40325.116.460.413.84003884014712050.71P-220/230V 50Hz
YED-M164AE-40436.824.2120.026.440041131015722050.71P-220/230V 50Hz
YED-M166AE-50235.626.9106.523.850021347023739701.83P-380/400V 50Hz
YED-M146AE-50346.535.1107.524.050032316030759701.83P-380/400V 50Hz
YED-M146AE-50458.043.7143.331.750043088032769701.83P-380/400V 50Hz
YED-M166AE-50470.553.1213.346.850042694029769701.83P-380/400V 50Hz


YED-C Series(fin spacing=7mmR404A)

TypeSC2SC3SurfaceTube volume
Fan

Fan Qty.

Air
flow

Air throw
NoiseFan InputFan Current
Fan Supply Power
(kW)(kW)(m2)(l)φ(mm)(m3/h)(m)(dB(A))(W/pcs)(A/pcs)
YED-M142CE-2522.92.312.04.425021640652550.31P-220/230V 50Hz
YED-M143CE-3024.53.617.96.430023090857850.31P-220/230V 50Hz
YED-M143CE-3036.85.427.09.2300346351259850.31P-220/230V 50Hz
YED-M164CE-40210.68.240.113.84002632013672050.71P-220/230V 50Hz
YED-M144CE-40313.010.140.413.84003952015692050.71P-220/230V 50Hz
YED-M164CE-40421.216.580.426.440041264016702050.71P-220/230V 50Hz
YED-M166CE-50224.515.471.423.850021574027739701.83P-380/400V 50Hz
YED-M146CE-50328.317.672.024.050032597032759701.83P-380/400V 50Hz
YED-M146CE-50437.723.495.831.750043462034769701.83P-380/400V 50Hz
YED-M166CE-50448.530.5142.746.850043148033769701.83P-380/400V 50Hz


YED-D Series(fin spacing=10mmR404A)

TypeSC3SC4SurfaceTube volumeFan
Fan Qty.

Air
flow

Air throw
NoiseFan InputFan Current
Fan Supply Power
(kW)(kW)(m2)(l)φ(mm)(m3/h)(m)(dB(A))(W/pcs)(A/pcs)
YED-P144DE-5028.56.152.414.550021858036768701.73P-380/400V 50Hz
YED-P164DE-50210.97.879.121.850021759035768701.73P-380/400V 50Hz
YED-P144DE-50312.89.179.121.450032787040778701.73P-380/400V 50Hz
YED-P144DE-50417.012.1105.529.150043716044788701.73P-380/400V 50Hz
YED-P164DE-50421.815.6158.342.850043518042788701.73P-380/400V 50Hz
YED-P144DE-50521.315.2131.935.650054645048808701.73P-380/400V 50Hz
YED-P164DE-50527.319.4197.952.750054397546808701.73P-380/400V 50Hz



SC1-Air Inlet temperature=10℃DT=10KRH-85%Overheat=6.5K;
SC2-Air Inlet temperature=0℃DT=8KRH-85%Overheat=5.2K;
SC3-Air Inlet temperature=-18℃DT=7KRH-95%Overheat=4.6K;
SC4-Air Inlet temperature=-25℃DT=6KRH-95%Overheat=3.9K;

The data refer to sound pressure level(1m)

Ⅱ.Refrigerant correction factors

RefrigerantSC1SC2SC3SC4
R134a0.930.910.85
R507A0.970.970.970.97
R404A1111


Ⅲ.Connection pipe standard

Pipe diameter comparison(SI/BS)MetricφmmImperialφ"
227/8
281-1/8
351-3/8
421-5/8
542-1/8


Ⅰ.Working conditions

Note1: SC1-Air Inlet temperature=10℃DT=10KRH-85%Overheat=6.5K;
SC2-Air Inlet temperature=0℃DT=8KRH-85%Overheat=5.2K;
SC3-Air Inlet temperature=-18℃DT=7KRH-95%Overheat=4.6K;
SC4-Air Inlet temperature=-25℃DT=6KRH-95%Overheat=3.9K;

Note2: The data refer to sound pressure level(1m)

Ⅱ.Refrigerant correction factors

RefrigerantSC1SC2SC3SC4
R134a0.930.910.85
R507A0.970.970.970.97
R404A1111


Ⅲ.Connection pipe standard

Pipe diameter comparison(SI/BS)MetricφmmImperialφ"
227/8
281-1/8
351-3/8
421-5/8
542-1/8



Dimensionselectric defrost heaterWeights

TypeDimensionsConnectionDrain outletElectric defrost(kW)Mass(kg)
ABCDE0E01E1E2E3E4E5FInletOutletCoilTraySupplyNet weightGross weight
YED-M142AE-25213604304003701030//////1351/27/8G12.01.11P-220
/230V 50Hz
3445
YED-M142CE-2522.01.13345
YED-M143AE-30215605304703701230//////1/21-1/82.41.34457
YED-M143CE-3022.41.34456
YED-M143AE-30321605304703701830//////5/81-3/83.21.66277
YED-M143CE-3033.21.66176
YED-M164AE-40218706305504401530//////1405/81-3/85.21.57892
YED-M164CE-4025.21.57691
YED-M144AE-403262063055044022801500/////5/81-5/85.82.0101119
YED-M144CE-4035.82.094112
YED-M164AE-404337063055044030301500/////7/81-5/89.31.9163166
YED-M164CE-4049.31.9140163
YED-M166AE-50224157357155552030/10001030///1507/81-5/8G1 1/410.21.2134168
YED-M166CE-50210.21.2131165
YED-M146AE-50334157357155553030/100010001030//7/82-1/8G1 1/210.52.2164205
YED-M146CE-50310.52.2161202
YED-M146AE-50444157357155554030/1000100010001030/7/82-1/8132.4213261
YED-M146CE-504132.4209257
YED-M166AE-5041-3/82-1/819.82.4248296
YED-M166CE-50419.82.4242290
YED-P144DE-50224158207056352030/10001030///5/81-3/8G1 1/494.2116150
YED-P164DE-5025/81-5/810.84.2132166
YED-P144DE-50334158207056353030/100010001030//5/81-5/8G1 1/213.85.3164205
YED-P144DE-50444158207056354030/1000100010001030/7/82-1/817.46.8212260
YED-P164DE-5047/82-1/8216.8244292
YED-P144DE-50554158207056355030/100010001000100010307/82-1/821.68260315
YED-P164DE-5057/82-1/824.68299354